CISA/Hitachi Energy advisory: multiple vulnerabilities in RTU500 CMU Firmware (CVSS up to 8.8)
CISA republished a Hitachi Energy PSIRT advisory covering seven vulnerabilities (CVE-2026-17539, CVE-2026-28388, CVE-2026-6732, CVE-2026-6653, CVE-2026-6276, CVE-2026-9079, CVE-2026-11856, CVE-2026-8927, CVE-2026-8932) affecting RTU500 series CMU Firmware versions 12.7.1-12.7.7, 13.5.1-13.5.4, 13.6.1-13.6.3, 13.7.1-13.7.8, and 13.8.1-13.8.2. The issues stem from NULL pointer dereference, type confusion, use-after-free, and credential/cleartext handling flaws in embedded OpenSSL, libxml2, and libcurl components, and can cause denial of service or credential exposure on energy-sector RTU devices.
SECURITY · NETWORK · VULNERABILITY · SECURITY ADVISORY
PUBLISHED OCT 23, 2026 19:48 UTC
WHAT CHANGED
Hitachi Energy disclosed nine CVEs across multiple CWE categories (NULL pointer dereference, type confusion, use-after-free, cleartext transmission, insufficiently protected credentials, authentication bypass by capture-replay, authentication bypass by primary weakness) impacting specific version ranges of RTU500 series CMU Firmware. Vendor fixes are available: update to CMU Firmware 13.9.1 for most affected branches, or to 12.7.8 for the 12.7.x branch; fixes for 13.7.x (13.7.9) and 13.8.x (13.8.3) are noted as upcoming or available. CISA republished the vendor's CSAF advisory verbatim on 2026-10-20 after initial vendor publication on 2026-09-01 and an update on 2026-09-29 regarding the 12.7.8 fix.
WHY IT MATTERS
RTU500 devices are used worldwide in energy-sector industrial control systems; successful exploitation could disrupt IEC 60870-5-104 communications (denial of service), expose authentication or proxy credentials, or bypass intended TLS/authentication configurations via reused libcurl connections. Administrators operating affected firmware versions should prioritize patching given CVSS scores reaching 8.8, and should apply standard ICS network isolation and VPN-based remote access practices in the interim.
WHO IS AFFECTED
- PRODUCTS
- Hitachi Energy RTU500 ProductRTU500 series CMU Firmware
- CONFIGURATIONS
- CMU Firmware 13.5.1–13.5.4CMU Firmware 13.6.1–13.6.3CMU Firmware 13.7.1–13.7.8CMU Firmware 13.8.1–13.8.2CMU Firmware 12.7.1–12.7.7
- REGIONS
- Worldwide
- ENVIRONMENTS
- Energy sector critical infrastructure
WHAT TO DO
- 01HIGH
Update RTU500 CMU Firmware versions 13.5.1–13.5.4 and 13.6.1–13.6.3 to version 13.9.1.
- 02HIGH
Update RTU500 CMU Firmware versions 13.7.1–13.7.8 to version 13.9.1, or to 13.7.9 when it becomes available.
- 03HIGH
Update RTU500 CMU Firmware versions 13.8.1–13.8.2 to version 13.9.1 or 13.8.3.
- 04HIGH
Update RTU500 CMU Firmware versions 12.7.1–12.7.7 to version 12.7.8, or upgrade directly to version 13.9.1.
- 05HIGHAUTOMATABLE
Minimize network exposure of RTU500 devices and ensure they are not directly accessible from the internet.
- 06MEDIUM
Place RTU500 control system networks and remote devices behind firewalls, isolated from business networks.
- 07MEDIUM
Require VPN use for any remote access to RTU500 systems, keeping VPN software updated to the latest version.